 DRA240 SERIES
AC - DC DIN RAIL MOUNTABLE 240W INDUSTRIAL CONTROL EQUIPMENT
FEATURES
COMPACT DESIGN HIGH EFFICIENCY UP TO 90% P .F.C. FUNCTION AVAILABLE PARALLEL FUNCTION AVAILABLE (SWITCH) INPUT VOLTAGE 115/230VAC AUTO SELECT
SELECTION CHART
DRA 240 - 24 x
Wattage A : SCREW TERMINALS B : DETACHABLE CONNECTOR 24 : 24V OUT 48 : 48V OUT
MODEL LIST
MODEL NO.
DRA240-24x DRA240-48x
INPUT VOLTAGE
115 / 230 VAC 115 / 230 VAC
OUTPUT OUTPUT WATTAGE VOLTAGE Single Output Models
240 WATTS 240 WATTS + 24 VDC + 48 VDC
OUTPUT CURRENT
10A 5A
EFF. (min.)
87% 88%
EFF. (typ.)
89% 90%
SPECIFICATION
All Specifications Typical At Nominal Line, Full Load, 25oC Unless Otherwise Noticed
GENERAL
Characteristics
Isolation voltage Isolation resistance Ambient temperature Derating Storage temperature Relative humidity Dimension Cooling Case material
Conditions Conditions
Input / Output Input / Output, @ 500VDC Operating at Vi nom Vi nom, from +61 to +71 C Non operational Vi nom, Io nom Screw terminal type Detachable connector type Free air convection Metal
o
min. min.
3,000 100 -25 -25 20
typ. typ.
max. max.
unit unit
VAC M
+ 71 2.5 + 85 95
o o
C C
%/ C
o
% RH mm mm mm
L123.6 x W83 x D123.6 L142 x W83 x D123.6
www.chinfa.com 2008.09.23
sales@chinfa.com
DRA240 SERIES
SPECIFICATION
All Specifications Typical At Nominal Line, Full Load, 25oC Unless Otherwise Noticed
INPUT SPECIFICATIONS
Characteristics
Rated input voltage Input voltage range Io nom Ta min ... T max, AC in 115V selected a Io nom AC in 230V selected
DC in
Conditions
min.
93 186 210
typ.
max.
132 264 370
unit
VAC VAC VAC VDC A Hz A A
115 / 230(auto select)
Rated input current Line frequency Inrush current P F. C. .
Io nom Vi nom, Io nom Vi nom, Io nom Vi : 230VAC, Io nom Vi : 115VAC Vi : 230VAC 47
5.4 / 2.2 63 30 60 0.7
OUTPUT SPECIFICATIONS
Characteristics
Output voltage accuracy
(Adjusted before shipment)
Conditions
Vi nom, Io max Vi nom Io nom, Vi min ...Vi max Vi nom, Io min ...Io nom Vi nom, Io min Vi nom, Io nom,BW = 20MHz Vi nom, Io nom Vi nom, Io nom Vi nom, Io nom Vi nom, Io nom 0.9 Io max Vi nom, Io nom, Po / Pi Vi = 115VAC Vi = 230VAC 24V models 48V models 24V models 48V models 24V models 48V models single mode parallel mode
min.
-0 0
typ.
max.
+1 0.5 1 5 0.02 100
unit
% % % % % % / oC mV ms ms
Minimum load Line regulation Load regulation Temperature coefficient Ripple & noise Hold up time Voltage trim range
16 25 30 22.5 47 17.6 37 17.6 37 Up to 90%, See model list 28.5 56 19.4 43 19.4 43 3
VDC VDC VDC VDC VDC VDC unit
DC ON indicator threshold at start up DC LOW indicator threshold after start up Parallel operation Efficiency
CONTROL AND PROTECTION
Characteristics
Input fuse Rated over load protection Power Rdy (for 24V model only) Vi nom
Threshold voltage of contact closed(at start up) Electrical isolation Contact rating at 60VDC
Conditions
min.
120 17.6 500
typ.
max.
145 19.4 0.3
unit
% VDC VDC A %
T6.3A / 250VAC internal
Over voltage protection Output short circuit
Vi nom, Io nom Vi nom, Io nom
120 Current limited
145
www.chinfa.com 2008.09.23
sales@chinfa.com
DRA240 SERIES
SPECIFICATION
All Specifications Typical At Nominal Line, Full Load, 25oC Unless Otherwise Noticed
APPROVALS AND STANDARDS
UL / cUL TUV CE UL508 Listed, UL60950-1 Recognized EN60950 EN61000-6-3, EN55022 class B EN61000-3-2, EN61000-3-3 EN61000-6-2, EN55024 EN61204-3
CIRCUIT SCHEMATIC
Block diagram for DRA240 series
L Fuse Filter N Y
Inrush Current Limiter, Rectifier and Auto Select 115 / 230 Vac
Vo + P. F. C. Circuit
Smoothing Circuit Switching
Device
Rectifier
Current Detection
Vo Single / Parallel Select Vout ADJ.
PWM Controller
Opto Isolation Opto Isolation
Reference & Error Amp. Over Voltage Detection Output Level Detection
Note: 1) For 24V Model Only
DC ON (Green LED) DC LOW (Red LED) RDY 1) (Relay Contact)
PHYSICAL CHARACTERISTICS
CASE SIZE
SCREW TERMINAL TYPE DETACHABLE CONNECTOR TYPE 123.6 x 83 x 123.6 mm (4.87 x 3.27 x 4.87 inches) 142 x 83 x 123.6 mm (5.59 x 3.27 x 4.87 inches)
WEIGHT
1100g
www.chinfa.com
2008.09.23
sales@chinfa.com
DRA240 SERIES
MECHANISM & PIN CONFIGURATION
mm [inch]
CONSTRUCTION
83 [3.27]
6 1
83 [3.27]
116.6 [4.59]
7.0 [0.3]
Easy snap-on mounting onto the DIN-Rail (TS35/7.5 or TS35/15), unit sits safeIy and firmly on the rail.
6
1
S P
- - ++ Rdy
Vout ADJ.
123.6 [4.87]
DC LO DC ON
S P
- - ++ Rdy
Vout ADJ.
123.6 [4.87] 142 [5.59]
DC LO DC ON
INSTALLATION
Ventilation / Cooling Normal convection All sides 25mm free space For cooling recommended Connector size range Screw terminal: 10-24AWG flexible / solid cable, 8 m/m stripping at cable end recommends Detachable connector: 14-24AWG flexible / solid cable, 7 m/m stripping at cable end recommends
DRA240
L N
DRA240
L N
AC INPUT
7 9 7 9
PIN ASSIGNMENT
PIN NO.
1 2 3 4 5 6 7 8 9
Designation
RDY
Description
A normal open relay contact for DC ON level control (Never connect except 24V model) Positive output terminal Positive output terminal Negative output terminal Negative output terminal Ground this terminal to minimize high-frequency emissions Input terminals (phase conductor, no polarity at DC input) Input terminals (neutral conductor, no polarity at DC input) Operation indicator LED DC LOW voltage indicator LED Trimmer-potentiometer for Vout adjustment Single / Parallel select switch
OUT
V+ V+ VV-
IN
L N DC ON
OTHER
DC LO Vout ADJ. S/P
DERATING
100 Power out [ % ] 75
0 -25 www.chinfa.com
2008.09.23
Temperature [ oC ]
61
71 sales@chinfa.com


▲Up To Search▲   

 
Price & Availability of DRA240-24A

All Rights Reserved © IC-ON-LINE 2003 - 2022  

[Add Bookmark] [Contact Us] [Link exchange] [Privacy policy]
Mirror Sites :  [www.datasheet.hk]   [www.maxim4u.com]  [www.ic-on-line.cn] [www.ic-on-line.com] [www.ic-on-line.net] [www.alldatasheet.com.cn] [www.gdcy.com]  [www.gdcy.net]


 . . . . .
  We use cookies to deliver the best possible web experience and assist with our advertising efforts. By continuing to use this site, you consent to the use of cookies. For more information on cookies, please take a look at our Privacy Policy. X